| OCR Text |
Show Manti The proposed retaining wall between the Plan III and Plan D5lD does not add to trle ap})earanoe of the buildir:g group. A simple transi" tion fran. the lawn between the buildings v«>uld accomplish the purpose ot mnd11ng the chaneing erade satisfactorily. Plan. t5lE - Office ~nd ,Bedroom: This bu11dinr; is nearing completion. All ca~nter work is satisfaotory. The mter:1aJ.s used generally are quite satisfactory. This build1ng will have a used to11et a.tld lavatory fixture in a toilet room whioh bus been added. The building bas cEment porches. The woodwork is enameled and the walla are to be covered with plastic paint. It ,vas noticed that the front door tread. waG graded toward the otfice room. This should be sh1rnned up to eive a drain off to the outside. There are three outlets provided for lights in the front parch ce1ling. Only OM 1s necessary. The other two should be covered with pI'OplIr. outlet box plates. There 1s no light outlet provided for the back porch and this should be taken care of. The grode at the north side of this building ls to be l~ored to s ecure at least 8" of exposed foundat1oni Plan #21 - Two-Ca,r ,Garage and Storeroom! r.rhis building 15 The carpenter work 1s acoeptable. The concrete work is fro:m. fair good. Too conorete floor is very rough finish. Somr; nativo material has been used in this building and SOlm of t}-l.,e shiplap is sh.riludll{"'; badly. Tnls is another case \'lhere inspection of rr..ateriala 11..9.8 failed to saw extent. Rejoction should have been rede of the shiplap furnished for this WOrk. This building has a chimney and in view of the ECt{ safety regula tion, I believe it wise to avoid the use of this ch1mney at least until we can Cet H satisfactory ruling on wr.at is desired fol' safety rneasu.:i."'OS in buHdil1.e where equiprent using casaline is stored. com:plet~, too E<lulj;mont Shed ... Road Manual ;Plan: This building has a concrete floor and is covered wi t h Gal1IDn1~ed iron. Reference is ma.de to Mr. Vloods t letters and othercOITespOndence at April 27, May 2, and May 8. Native material has been used tor the franv:; of this bu1lding. The doors are yet to be finiS hed and hu.'lg. The bul1din:-3 needs venUla"'; tors at the ends of' the Gables and the cornice is to be eanpletad on this building to make it more finished in appearanc'c and so that it will be possible to paint the cornice. Tr~ entire buildlr~ is to be painbad and. it is suggested that before painting work starts. that the builctlng be carefully gone over with a vinegar solution so t:r..at paint ma:y be pro.r;>erly applied. The sheet lMtal is galvanized and this will react with the vineGar in sueh a IllP,Jl.ller that a bond may be secured with the paint. If. after the application of fully cleaned with other solvonts where required. The tin sh~Jld be given Dna ooat of pa1nt composed ot 10 lbs. of Venetion red. 1 lb. of red lead. and 1 gal. of pure linseed oil. The following coats my bo of s t andard p1int recomm.ended for our Build.ing work in the building plans and Ma."lual. |