OCR Text |
Show "Open Ground Flare systems - Hystorical review of a recent project from the concept to the commissioning, passing through R&D activities Presentation and Discussion of the Results of R&D activities as a basis for design and execution stage." Enrico Giovanardi Engineering Manager Flares, Thermal Oxidisers and Acid Gas Burners Hamworthy Combustion Italy AFRC 2011 Open Ground Flare systems Technical Paper 1. Foreword The more and more restrictive environmental laws and regulation applied in most of the projects all over the world led in the last years to the need to increase on one hand smokeless performances of assisted flares, to guarantee smokeless combustion up to Ringelmann 0, and, on the other hand to install staged enclosed ground flares or staged opened ground flare with totally hidden flames to avoid visible flames. Hamworthy was awarded from Petrobras - Brasil for the Design of the biggest ground flare of South America, disposing 750 Tons/Hr of hydrocarbon. This presentation will show, as a key study, the development of the project, the highly successfully results achieved and the synergies shared between the involved disciplines like CFD analysis and modelisation, tests and test rig preparation, design and prototype fabrication, radiation software prediction and validation against data acquired, postprocessing site testing and site acceptance test. The full presentation shall detail all the following shortened subjects of this technical paper, with exposure of pictures and short videos. 2. Presentation Content System description Mechanical & Structural Design vs. Process and Thermal Design 3D Modelling Flare/Burners Prototype Testing CFD Simulation Commissioning Lesson learnt AFRC 2011 Open Ground Flare systems Technical Paper 2. System description The designed ground flare consists mainly in the following parts a. b. c. d. e. f. A staged Wet Flare disposing 750 Tons/Hr of hydrocarbons at max. rate. A smaller staged Cold Flare disposing 149 Tons/Hr of hydrocarbons at max.rate. A Fence with perimeter of 68x62 mt. and 18 mt. Height, enough to totally hide the flames. 307 "Spider" burners (300+7 wet+cold flare), shared on 6+2 stages (wet + cold flare) Staging System Automatic FFG/HE Pilot ignition system with Fuel Skid & PLC for ignition control 3. 3D Modelling System was designed 100% with aid of 3D modelling to harmonise all involved disciplines AFRC 2011 Open Ground Flare systems Technical Paper 4. Simulating to scale test rig To finalise process design: a. Burner Type and Drilling was first selected with single burners firing tests b. Selected burner/drilling was again tested with different type of fuels from methane to heavy unsaturated hydrocarbons (Propylene) c. a to scale Ground Flare was built to perform flaring testing under different conditions The flame length - Propane - Test#1 AFRC 2011 Open Ground Flare systems Technical Paper 5. CFD CFD of Ground Flare emission has been simulated on large scale 6. Commissioning Ground Flare has been tested at 90% of its Design capacity ______________________________________________________________________________ Enrico Giovanardi is Flares and Thermal Oxidiser Engineering Manager at Hamworthy Combustion Italy. He has an MSc degree in Aerospace Engineering from Politecnico of Milan (Italy) and 15 years experience in design of combustion equipment. AFRC 2011 Open Ground Flare systems Technical Paper |